Stay up to date with Georgia Energy Code 2020 application solutions for commercial lighting. Support for a basis of design is provided by SESCO Lighting Georgia and Legrand WattStopper.

Georgia Energy Code 2020 was adopted January 1, 2020. The energy code commercial lighting control sections follow IECC2015 without additional Georgia amendments.

See application basis of design references below. For any Georgia application questions, reach out to Adam Rixey, PE at SESCO Lighting Georgia.

cheatsheet
Georgia Energy Code 2020 Cheatsheet PDF

typical

  • Private Restroom
    • Dim Type: On/Off 1-Zone (Wallbox)
    • Keypad: Wallbox Occ Sensor (Line-Voltage)
    • Occ Sensor: Wallbox Occ Sensor (Line-Voltage)
    • Daylight Sensor: Not included in example
  • Small Private Office
    • Dim Type: On/Off 2+ Zone (Lighting Room Controller)
    • Keypad: Wallbox Occ Sensor (Low-Voltage)
    • Occ Sensor: Wallbox Occ Sensor (Low-Voltage)
    • Daylight Sensor: Not included in example
  • Large Private Office
    • Dim Type: On/Off 2+ Zone (Lighting Room Controller)
    • Keypad: Wallbox Occ Sensor (Low-Voltage)
    • Occ Sensor: Wallbox Occ Sensor (Low-Voltage)
    • Daylight Sensor: Not included in example
  • Breakroom/Kitchen
    • Dim Type: On/Off (Lighting Room Controller)
    • Keypad:
    • Occ Sensor:
    • Daylight Sensor: Not included in example
  • Classroom
    • Dim Type: 0-10V (Lighting Room Controller)
    • Keypad: On/Off/Raise/Lower Dim-Style
    • Occ Sensor:
    • Daylight Sensor: Not included in example
  • Conference Room
    • Dim Type: 0-10V (Lighting Room Controller)
    • Keypad: On/Off/Raise/Lower Dim-Style
    • Occ Sensor:
    • Daylight Sensor: Not included in example
  • Multi-Stall Restroom
    • Dim Type: On/Off
    • Keypad: On/Off Switch
    • Occ Sensor:
    • Daylight Sensor: Not included in example
  • Open Office
    • Dim Type: 0-10V (Lighting Room Controller)
    • Keypad: On/Off/Raise/Lower Dim-Style
    • Occ Sensor: Ceiling
    • Daylight Sensor: Yes
  • Small Conference Room
    • Dim Type: 0-10V (Lighting Room Controller)
    • Keypad: On/Off/Raise/Lower Dim-Style
    • Occ Sensor: Ceiling
    • Daylight Sensor: Not included in example
unswitched-control-devices

Private Restroom

Sequence Of Operations Example

  • Lighting and fan are manually controlled On/Off with occupancy sensor switch.
  • Lighting and fan will auto Off within 20 minutes of occupants leaving.

Layout Example

image of Private Restroom wired layout

Small Private Office

Sequence Of Operations Example

  • Lighting (a) auto On to 50% when occupancy detected.
  • Manaul On/Off and 50% reduction control of lighting (a,b) with wall switch occupancy sensor.
  • Auto Off all lighting within 20 minutes of occupants leaving.

Layout Example

image of Small Private Office wired layout

Large Private Office

Sequence Of Operations Example

  • Lighting auto On to 50% when occupancy detected.
  • Manual On/Off/Dim and reduction control of general lighting with dimmer switch.
  • Lighting will continuously dim based on daylight contribution to maintain at least 35FC at task level.
  • Auto Off all lighting within 20 minutes of occupants leaving.

Layout Example

image of Large Private Office wired layout

Breakroom/Kitchen

Sequence Of Operations Example

  • General lighting (a) auto On to 50% when occupancy detected.
  • Manual On/Off and 50% reduction control of general lighting (a, b) with wall switch occupancy sensor.
  • Manual On/Off control under cabinet lighting (c) with switch.
  • Auto off all lighting within 20 minutes of occupants leaving.

Layout Example

image of Breakroom/Kitchen wired layout

Classroom

Sequence Of Operations Example

  • General lighting (a, adz1) auto On to 50% when occupancy detected.
  • Manual On/Off/Dim and light reduction control of general lighting (a, adz1) with dimmer switches.
  • Manual On/Off/Dim white board lighting (b) with dimmer switch.
  • Lighting in daylight zone (adz1) will continuously dim based on daylight contribution to maintain at least 35FC at task level.
  • Auto Off all lighting within 20 minutes of occupants leaving.

Layout Example

image of Classroom wired layout

Conference Room

Sequence Of Operations Example

  • General lighting (a, adz1) auto On to 50% when occupancy detected.
  • Manual On/Off/Dim and reduction control of general lighting (a, adz1) and down lighting (b, c, d) with scene switches.
  • Scene settings:
  • - Scene 1: General Lighting (a, adz1) 100%, (b) 0% (c) 0%, (d) 0%
  • - Scene 2: Projection (a, adz1) 0%, (b) 75% (c) 50%, (d) 0%
  • - Scene 3: Conferencing (a, adz1) 50%, (b) 50% (c) 25%, (d) 50%
  • - Scene 4: All Off (a, adz1) 0%, (b) 0% (c) 0%, (d) 0%
  • Lighting in daylight zone (adz1) will continuously dim based on daylight contribution to maintain at least 35FC at task level.
  • Auto Off all lighting within 20 minutes of occupants leaving.

Layout Example

image of Conference Room wired layout

Multi-Stall Restroom

Sequence Of Operations Example

  • For each restroom independently, lighting (a) auto On to 50% and exhaust fan auto on when occupancy detected.
  • Manual On/Off and 50% reduction control of general lighting (a, b) with switches.
  • Auto Off all lighting and exhaust fans for each restroom independently within 20 minutes of occupants leaving.

Layout Example

image of Multi-Stall Restroom wired layout

Open Office

Sequence Of Operations Example

  • General lighting (a, adz1) auto On to 50% when occupancy detected.
  • Manual On/Off/Dim and reduction control of general lighting (a, adz1) with dimmer switches.
  • Lighting in daylight zone (adz1) will continuously dim based on daylight contribution to maintain at least 35FC at task level.
  • Auto Off all lighting within 20 minutes of occupants leaving.
  • Emergency lighting transfers to emergency power source and full On with loss of normal power.

Layout Example

image of Open Office wired layout

Small Conference Room

Sequence Of Operations Example

  • General lighting (a) auto On to 50% when occupancy detected.
  • Manual On/Off/Dim and reduction control of general lighting (a) and down lighting (b, c) with scene switch.
  • Scene settings:
  • - Scene 1: General Lighting (a) 100%, (b) 0% (c) 0%
  • - Scene 2: Projection (a) 0%, (b) 75% (c) 50%
  • - Scene 3: Conferencing (a) 50%, (b) 50% (c) 25%
  • - Scene 4: All Off (a) 0%, (b) 0% (c) 0%
  • Auto Off all lighting within 20 minutes of occupants leaving.

Layout Example

image of Small Conference Room wired layout

basis of design

WattStopper DLM Product Matrix Brochure PDF

Popular basis of design parts:

  • LMRC-101 new site
    • On/Off 20A relay Dimming Room Controller
    • 1-Circuit in, 1-Zone out
    • LMRC-100 Series
  • LMRC-102 new site
    • On/Off 20A relay Dimming Room Controller
    • 1-Circuit in, 2-Zones out
    • LMRC-100 Series
  • LMRC-111 new site
    • 0-10v 10A relay Dimming Room Controller
    • 1-Circuit in, 1-Zone out
    • LMRC-110 Series
  • LMRC-112 new site
    • 0-10v 10A relay Dimming Room Controller
    • 1-Circuit in, 2-Zones out
    • LMRC-110 Series
  • LMRC-211 new site
    • 0-10v 20A relay Dimming Room Controller
    • 1-Circuit in, 1-Zone out
    • LMRC-210 Series
  • LMRC-212 new site
    • 0-10v 20A relay Dimming Room Controller
    • 1-Circuit in, 2-Zones out
    • LMRC-210 Series
  • LMRC-213 new site
    • 0-10v 20A relay Dimming Room Controller
    • 1-Circuit in, 3-Zones out
    • LMRC-210 Series
  • ELCU-200 new site
    • UL924 Emergency Bypass Device
    • Use with LMRC-210 series dimming room controller's dim-to-100% on normal power loss
    • Emergency feed input provides the fixture power in all cases
    • Normal unswitched power input detects loss of power
    • Normal switched power input allows emergency relay to mimic room controller relay in normal conditions
  • LMDC-100 new site
    • Ceiling Mount, Dual-Tech Ultrasonic+PIR Occupancy Sensor
    • Configure as either occupancy sensor (auto on) or vacancy sensor (manual on)
  • LMDX-100 new site
    • Corner Mount, Dual-Tech Ultrasonic+PIR Occupancy Sensor
    • Configure as either occupancy sensor (auto on) or vacancy sensor (manual on)
  • LMDW-101 new site
    • Wallbox, Dual-Tech Ultrasonic+PIR Occupancy Sensor
    • Configure as either occupancy sensor (auto on) or vacancy sensor (manual on)
    • 1-Button for 1-zone on/off
  • LMDW-102 new site
    • Wallbox, Dual-Tech Ultrasonic+PIR Occupancy Sensor
    • Configure as either occupancy sensor (auto on) or vacancy sensor (manual on)
    • 2-Button which can be used for 2-zones on/off or 1-zone on/off/raise/lower
  • LMDM-101 new site
    • Dimming Low-Voltage Switch
    • On/Off/Raise/Lower
    • Available to use in practically all multi-way applications
  • LMSW-105 new site
    • Scene Dimming Low-Voltage Switch
    • On/Off/Raise/Lower for all zones
    • 4-scenes/presets, typically last is Off
    • Available to use in practically all multi-way applications
  • LMSW-101 new site
    • On/Off Low-Voltage Switch
    • LMSW-100 Series Low-Voltage Switches
    • Typically used for 1-zone or panel override
    • Available to use in practically all multi-way applications
  • LMLS-500 new site
    • Open-loop daylight sensor
    • Typically used in open-office style spaces
    • Provides up to 3-zones of dimming control with one sensor
    • Aligns up to 3-zones to primarily daylight and not electric light
  • LMLS-400 new site
    • Closed-loop daylight sensor
    • Typically used in private office style spaces
    • Provides 1-zone of dimming control with one sensor
    • Balances the combination of daylight and 1-zone of electric light
  • LMDI-100 new site
    • Serial data interface
    • Preferred by A/V contractors due to pre-coordinated fixed serial commands that typically act as a scene switch
  • LMCP8, LMCP24, LMCP48 new site
    • Capacity up to 8, 24, or 48 relays per panel
    • Not necessary to fill to capacity; spec a relay panel schedule as needed

WattStopper DLM Part Blocks PDF | DWG